Ashrae# | TradeName | Manufacturer | Replaces | Type | Composition (wt%) | GWP | Recommended Lubricant | Applications |
| R-410A | Forane® 410A | Arkema | R-22 | HFC Near-azeotropic blend | R-32 - 50% R-125 - 50% | 2,100 | POE | Replacement for R-22 in smaller size chillers, and residential and light commercial A/C systems. Never use as a retrofit for R-22 equipment. |
| | Genetron® AZ-20 Suva® 410A Puron® | Honeywell
Dupont |
| R-427A | Forane® 427A | Arkema | R-22 | HFC Zeotropic blend | R-32 - 15% R-125 - 25% R-143a - 10% R134a - 50% | 2,130 | MO orAB (with oil separator) POE | Recommended retrofit for R-22 in DX systems. Used in A/C, medium, and low temperature systems. |
| | | |
| R-407A | Forane® 407A | Arkema | R-22 | HFC Zeotropic blend | R-32 - 20% R0125 - 40% R-134a - 40% | 2,100 | POE | Replacement/retrofit for R-22 DX systems. Used in medium and low temperature refrigeration. |
| Suva® 407A Klea® 407A
| Dupont Ineos |
| R-407C | Forane® 407C | Arkema | R-22 | HFC Zeotropic blend | R-32 - 23% R-125 - 40% R-134a - 52% | 1,800 | POE | Replacement/retrofit for R-22 DX systems. Used in residential A/C, medium, and low temperature systems. |
| | Suva® 407C Genetron® 407C
| Dupont Honeywell |
| R-134a | Forane® 134a | Arkema | R-22 | HFC Single component fluid | R-134a - 100% | 1,430 | POE PAG (auto) | Replacement/retrofit for R-12 and R-500 systems. Recom-mended retrofit for R-12 automotive A/C systems. |
| | Suva® 134a Genetron® 134a Klea® 134a
| Dupont Honeywell
Ineos |
| R-404A | Forane® 404A | Arkema | R-502 R-22 R-402A R-408A | HFC Near-azeotropic blend | R-125 - 44% R-143a - 52% R-134a - 4% | 3,900 | POE | Replacement/retrofit for R-502 and R-22. Used in medium and low temperature refrigeration systems. |
| | Suva® 404A Genetron® 404A
| Dupont Honeywell
|
| R-507A | Forane® 507A | Arkema | R-502 R-22 R-402A R-408A | HFC Azeotropic blend | R-125 - 50% R-143a - 50% | 4,000 | POE | Replacement/retrofit for R-502 and R-22. Used in medium and low temperature refrigeration systems. |
| | Suva® 507A Genetron® AZ-50 | Dupont Honeywell |
| R-22 | Forane® 22 | Arkema | | HCFC Single component fluid | R-22 - 100% | 1,810 | MO AB | Used in A/C, medium, and low temperature systems. |
| | Suva® 22 Genetron® 22
| Dupont Honeywell |
| R-408A | Forane® 408A | Arkema | R-502 | HCFC Near-azeotropic blend | R-125 - 7% R-143a - 46% R-22 - 47% | 2,650 | MO AB POE | Recommended retrofit for R-502 systems. Used in medium and low temperature systems. |
| | Suva® 408A Genetron® 408A
| Dupont Honeywell |
| R-409A | Forane® 409A | Arkema | R-12 R-500 | HCFC Zeotropic blend | R-22 - 60% R-124 - 25% R-142b - 15% | 1,290 | MO AB POE | Recommended retrofit for R-12/ R-500 stationary DX systems. Used in medium and low temperature systems. |
| | Suva® 409A Genetron® 409A | Dupont Honeywell |
| R-123 | Forane® 123 | Arkema | R-11 | HCFC Single component fluid | R-123 - 100% | 77 | MO AB POE | Used in Centrifugal Chillers. Scheduled for phase-out. |
| | Suva® 123 Genetron® 123 | Dupont Honeywell |